Services

WALL & CEILING CONSTRUCTION

The wall and ceiling panel can be made out of following material as per customer requirement, al 1.6mm thick EGP steel panels backed by 12mm thick Gysum, b) Stainless steel SS304 panels, c) High. pressure Laminate panels as per EN standard, d) PUF sandwiched panel, The room wall will have two independent surface with minimum opening in between. The external wall of the room will be constructed with soild bricks with cements Plastering. The inner surfases walls will be constructed with 1.60 mm thick EGP steel panels backed by 12-mm gypsum board (India gypsum make) these panels will have flame resistance to Bs 1142 part 3. The inner surface wall will be fixed to the bricks all with Essential supports. There will be minimum possible cavitylgap in between the solid and steel walls. The total distance between the inside and outside surface of the operating room will be variable to suit the architect’s layout, but will be sufficient for the flush mounting of equipments 2400mm x 2800mm x 2800mm, as per theatre size.

AIR MANAGEMENT SYSTEM (PLENUM)

The laminar flow system shall comprise of the extruded aluminum profile frame. The complete unit will have factory prepared fine sealing system along with proper test certificates. The plenum will be suppled at silt duty sealed in factory made packing. The Cornars of the plenum will be made of extruded aluminum sections which support the fire retardant FRP housing in such a manner that the air is passed only through the deep pleat HEPA filter only. The laminar flow system will have SS perforated diffuser frill. The laminar flow system will have such design that it provides cleanliness of class 100. (<=100 particles/ft3) and bacteriological B (<=20cfu/m3).
Perfect tightness guaranteed by a between filters and holding structure enabling no by pass of HEPA Filters. Complete Filtration System will be factory assembled, tested and packed.
The absolute filters installed in the plenum will be suitable for applications for Laminar flow and clean rooms, these absolute filters will be dep pleat HEPA filters having extruded anodized aluminum, 69mm dep frame, and filter will provide flow uniformity exceeding +-.

1. Protective grids
White epoxy painted micro drawn grid
2. Separators
Continuous thermo plastic chord
3. Sealant
Polyurethane
4. Gasket
One piece polyurethane
5. EN 2822 class
H14
6. MPPS average efficiency
> 99.995%
7. MPPS average efficiency
>.gg 975%
8. 3 micron DOP efficiency
>_gg 999%
9. Final pressure drop
600 p’a (maximum)
10. Maximum operating Temperature
60 degree centigrade
11. Maximum RH
90 percent
12. Efficiency Test
Filters individually tested and certificated